Engineering Reference & ASME Code Basis
1. Core Formula & Variable Definitions
ANSI/ASA S12.2 Criteria for Evaluating Room Noise (Noise Criterion curves) · ASHRAE Handbook — HVAC Applications (recommended NC by space type)
Lp(fi) ≤ LNC(fi) → NC
dBA ≈ NC + 5…8
Octave bands fi ∈ {63, 125, 250, 500, 1000, 2000, 4000, 8000} Hz · NC = lowest clear NC-15…65 curve (ANSI/ASA S12.2 tangent) · ASHRAE space Pass/Fail
Field NC calculator using the ANSI/ASA S12.2 octave-band tangent method. Rated NC is the lowest standard curve (NC-15 to NC-65) that is nowhere exceeded by measured L_p. Pass/Fail uses ASHRAE HVAC Applications recommended maxima by space type. SpecRoutes: control-room-nc35, office-nc30, equipment-room-nc50, workshop-nc55. Estimated A-weighted level is a coarse NC+5…8 rule — not a substitute for calibrated dBA measurement. For rumble or tonal complaints, use RC or NCB analysis.
- L_p(f_i) (Octave-band SPL) — Sound pressure level in each standard octave band (dB).
- L_NC(f_i) (NC curve limit) — Published NC-15…65 octave-band limit at frequency f_i.
- NC (Noise Criterion rating) — Lowest NC curve that clears every band (tangent method).
- dBA est. (A-weighted estimate) — Screening: dBA ≈ NC + 5 to 8 dB.
2. Screening Rules Matching This Calculator
Rates NC by the ANSI/ASA S12.2 octave-band tangent method and compares to an ASHRAE space maximum. Calibrated dBA and RC/NCB remain site measurements.
Every octave band L_p(f_i) must sit at or below the chosen NC curve limit (tangent method).
Control Room, office, equipment room, and workshop presets set the recommended maximum NC.
Coarse A-weighted screening only — not a substitute for a calibrated sound-level meter.
Use RC or NCB analysis when low-frequency rumble or tonal complaints dominate.
Quick Reference Lookup Table
| NC | 63 Hz | 125 Hz | 250 Hz | 500 Hz | 1 kHz | 2 kHz | 4 kHz | 8 kHz |
|---|---|---|---|---|---|---|---|---|
| NC-15 | 47 | 36 | 29 | 22 | 17 | 14 | 12 | 11 |
| NC-20 | 51 | 40 | 33 | 26 | 22 | 19 | 17 | 16 |
| NC-25 | 54 | 44 | 37 | 31 | 27 | 24 | 22 | 20 |
| NC-30 | 57 | 48 | 41 | 35 | 31 | 29 | 28 | 27 |
| NC-35 | 60 | 52 | 45 | 40 | 36 | 34 | 33 | 32 |
| NC-40 | 64 | 56 | 50 | 45 | 41 | 39 | 38 | 37 |
| NC-45 | 67 | 60 | 54 | 49 | 46 | 44 | 43 | 42 |
| NC-50 | 71 | 64 | 58 | 54 | 51 | 49 | 48 | 47 |
| NC-55 | 74 | 67 | 62 | 58 | 56 | 54 | 53 | 52 |
| NC-60 | 77 | 71 | 67 | 63 | 61 | 59 | 58 | 57 |
| NC-65 | 80 | 75 | 71 | 68 | 66 | 64 | 63 | 62 |
Values from the ANSI/ASA S12.2 NC curve family used for FEK tangent screening. Verify against the current published standard for final HVAC design.
3. Applicability & Space Limits
NC screening applies to occupied HVAC spaces with measured octave-band spectra. Metallurgy is not applicable — limits are acoustic / space criteria.
| Group / Regime | Range / Condition | Limit / Criterion | Engineering Notes |
|---|---|---|---|
| Quiet occupied rooms | N/A — acoustic criterion | Typical max NC-25…35 | Control rooms, executive offices, and similar ASHRAE quiet spaces. |
| General offices / classrooms | N/A | Typical max NC-30…40 | Speech intelligibility driven; verify project ASHRAE table. |
| Equipment / mechanical rooms | N/A | Typical max NC-45…55 | Higher NC allowed; still rate the spectrum — do not skip NC for “loud rooms.” |
| Tonal / rumble complaints | N/A | Out of scope (use RC / NCB) | NC tangent can miss low-frequency or tonal issues that RC/NCB catch. |
Code Applicability & Safety Boundaries
- ANSI/ASA S12.2 tangent NC only — not a full room-acoustics model
- ASHRAE maxima are recommended screening values; project specs may be stricter
4. Step-by-Step Worked Example
Field VerificationShowHide
Worked example — Control Room NC-35 duty
Rate a control-room octave-band spectrum that sits on the NC-35 tangent profile and check ASHRAE Pass/Fail.
Compare each band to NC curves
Find lowest clear curve
Space compliance
5. How to calculate Noise Criterion (NC) rating
- 1
Select space type
Choose Control Room, Executive Office, Equipment Room, or Workshop to set the ASHRAE max NC for Pass/Fail.
- 2
Enter octave-band SPL
Input L_p (dB) for 63 Hz through 8000 Hz from a sound-level meter or HVAC report.
- 3
Read NC hero and compliance
Hero shows NC-XX and Pass/Fail versus the selected space limit.
- 4
Review tangent band and chart
Use the spectrum vs NC curve chart and octave-band rows to see which band governs the rating.
6. Frequently Asked Questions & Technical References
ShowHide
An NC calculator rates room noise by the ANSI/ASA S12.2 octave-band tangent method: find the lowest NC-15…65 curve that is nowhere exceeded by measured $L_p$, then compare to an ASHRAE space maximum. FEK SpecRoute /control-room-nc35 is the default Control Room path.
An NC rating is the lowest standard NC curve (NC-15 to NC-65) that is nowhere exceeded by measured octave-band sound pressure levels, per ANSI/ASA S12.2 tangent method.
Pass/Fail compares the rated NC to an ASHRAE HVAC Applications screening maximum for the selected space (e.g. Control Room NC-35, Office NC-30, Equipment Room NC-50, Workshop NC-55).
No. The tool reports a screening estimate dBA ≈ NC + 5…8 dB. Use a calibrated A-weighted measurement for compliance documentation.
For low-frequency rumble or tonal noise isolation, perform RC (Room Criterion) or NCB (Balanced Noise Criterion) analysis — NC alone can miss those complaint modes.